Additional specifications and description
Visual indication of the air quality
This HVAC transmitter offers a clear, visual indication of the TVOC level via the green, yellow and red LED. The green LED indicates that the TVOC level is within range - there is sufficient ventilation. When the TVOC level enters the alert range, the yellow LED lights up. Red means: TVOC out of range or insufficient ventilation. The measured temperature, relative humidity and TVOC level are available via the three analogue outputs and via Modbus RTU. Ambient light level is available via Modbus RTU.
How to control indoor air quality?
The measured temperature, relative humidity and TVOC level are available via the three analogue outputs and via Modbus RTU communication. The calculated dew point and the ambient light level are available via Modbus RTU communication. TVOC or Total Volatile Organic Compounds evaporate from substances such as cleaning products, adhesives, paints, etc. VOCs are also emitted from humans and animals. That is why a TVOC sensor provides a good, overall image of air quality. TVOC sensors are the best choice to control a ventilation system in residential environments. When more fresh air is required, the sensor will increase the fan speed or open the damper.
4-wire connection
This sensor offers you the choice to connect it via the cage clamp terminal blocks or via the RJ45 connector. Supply voltage and Modbus RTU communication can be connected via the RJ45 connector. Via the terminal blocks it is possible to connect the outputs, Modbus RTU communication and the supply voltage. Never connect the supply voltage via the RJ45 connector and the terminal blocks simultaneously! The supply voltage is 24 VDC. The ground terminals of the power supply (V-) and output (GND) are internally not connected. This means that a 4-wire cable is required to connect this sensor. Most 24 VDC power supplies offer protection against short circuit, overload and overvotage. A 24 VDC supply voltage increases the safety and reliability of your installation.
Easy to use!
This sensor doesn't require configuration. Once installed, it is ready to use. The default settings will do for most applications. If necessary, these settings can be adjusted via Modbus RTU. For example, a different output type can be selected to make it compatible with other devices: 0-10 VDC / 0-20 mA / 0-100 % PWM. Also the light intensity of the LEDs for status indication is adjustable. The Modbus register map provides a complete overview of all adjustable settings.
Each sensor is calibrated and tested in our factory.
In the unlikely event of TVOC sensor element failure, this module can be replaced. We use sensor elements and components of high quality. This ensures the long-term stability and accuracy of this HVAC transmitter. The enclosure offers an IP30 protection against ingress of dust and moisture. It can be mounted on a wall indoors. To ensure optimal performance, it should be protected from direct sunlight.