What is the maximum cable length for a Modbus RTU network?

Modbus RTU – how to interconnect Sentera devices
We recommend that the total cable length per segment does not exceed 1.000 m. (Total cable length = sum of the main network line and all branches).

Modbus RTU should follow a line topology, so avoid making branches on the main line. If branches are present, they should be kept as short as possible. The combined length of all branches should not exceed 20 m.

When the total cable length becomes too high, the Modbus RTU communication will be disturbed. To compensate these communication losses due to cable length, a Modbus repeater (e.g. DPOM-24-20) can be used to compensate cable length.
Recent news
Date 16/07/2021
Indoor Air Quality in hospitals
Indoor Air Quality in hospitals Why is air quality in hospitals so important? A hospital is a place where both weak and healthy people come into close contact with each other. In Corona times, that is a frightening scenario that requires many precautions to make this possible in safe conditions. Monitoring indoor air quality is one of these precautions. >>>
Date 25/05/2021
CO2 monitoring in schools
CO2 monitoring in schools Sentera CO2 meters help to reduce the spread of the COVID-19 virus in this school in Sint-Niklaas, Belgium. >>>
Date 16/03/2021
CO2 monitoring system to reduce the risk of COVID-19 contamination
CO2 monitoring system to reduce the risk of COVID-19 contamination Fresh indoor air reduces the risk of COVID-19 contaminations. Sentera HVAC sensors check whether there is sufficient fresh air supply. The measurements can be visualised via a 5-inch touchscreen. >>>