Can I control multiple motors with one fan speed controller?
Motor and fan related questions
Yes, that is possible.

If doing so, make sure that:
- All connected motors are identical.
- The fan speed controller is selected, based on the total motor current required, by adding together the rated current of all the connected motors. The selected fan speed controller must have a maximum current rating that is equal or higher than this sum.
- Each motor is protected by an individual thermal overload.
- The motors remain permanently connected to the fan speed controller and are not individually started or stopped whilst the fan speed controller is enabled.
- When using a frequency inverter: operate in V/F Mode only and apply an output filter.

In the scenario of one fan speed controller per motor, each motor can be controlled separately and run at a different speed. This is not the case when multiple motors are controlled via one fan speed controller. Secondly, running multiple motors from one fan speed controller creates a single point of failure.
Recent news
Date 09/07/2020
Brand new SDX fan speed controllers
Brand new SDX fan speed controllers The SDX infinitely variable fan speed controllers regulate the speed of small, single phase AC motors up to 3 Amps. Not only has the design of the enclosure been modernised, but also the electronics are brand new and offer many benefits. Especially the quieter motor operation at low speed is remarkable. >>>
Date 22/06/2020
How to measure indoor air quality?
How to measure indoor air quality? Sentera air quality sensors measure TVOC and equivalent CO2 level >>>
Date 15/06/2020
Electronic fan speed controllers
Electronic fan speed controllers Fan speed control for voltage controllable AC motors >>>
VK Icon
LinkedIn Icon
Follow us on
© 2020 Sentera. Powered by Bea Solutions