Sprite icons
Sentera uses cookies !
Privacy policy
Logo Sentera
Sentera – your partner in HVAC control solutions
right
White plastic enclosure with LED indicators and airflow openings
right
White plastic enclosure with LED indicators and airflow openings
White plastic enclosure with LED indicators and airflow openings
White plastic enclosure with LED indicators and airflow openings
White plastic enclosure with LED indicators and airflow openings
White plastic enclosure with LED indicators and airflow openings
Electronic circuit board in black plastic enclosure

CO | NO2 controller | wall mounting | LED indicators, 24 VDC


Product description

Indoor toxic gas sensor to control damper position or fan speed. The supply voltage is 24 VDC. It measures temperature, relative humidity, CO, NO2 and ambient light. The sensor algorithm controls the single output based on the measured values. This single output can be used to directly control an EC fan, an AC fan speed controller or a damper actuator. The default output type is 0-10 V. Different output types can be selected. All measurements and the control output value are available via Modbus RTU. The CO / NO2 sensor element is replaceable. All settings can be adjusted via Modbus RTU. Also the light intensity of the LEDs for status indication is adjustable. The enclosure can be wall mounted and offers an IP30 protection against ingress of dust and moisture.

Article code
RCCOF-R
GTIN
0.540.100.301.821.7
Category
Room CO - NO2 sensors
Available
Current stock
5 U.
Factory lead time
5 Week(s)

Additional specifications and description

 
Is there sufficient fresh air supply?
This CO sensor offers a clear, visual indication of the air quality via the green, yellow and red LED. The green LED indicates that the CO level is within range - there is sufficient fresh air supply. When the CO level enters the alert range, the yellow LED lights up. Red means: CO out of range or insufficient fresh air supply. The measured temperature, relative humidity, CO, NO2 and ambient light level are available via Modbus RTU.
 
How to control fresh air supply?
The output of this sensor can control an EC fan, an AC fan speed controller or a damper actuator. The output value varies proportionally in function of the measured temperature, humidity and CO concentration. When more fresh air is required, the sensor will increase the fan speed or open the damper.
 
4-wire connection
The cage clamp terminal blocks reduce wiring and installation time. They eliminate the need for routine maintenance and guarantee a reliable contact for solid or stranded wires. The supply voltage is 24 VDC. The ground terminals of the power supply (V-) and output (GND) are internally not connected. This means that a 4-wire cable is required to connect this sensor. Most 24 VDC power supplies offer protection against short circuit, overload and overvoltage. A 24 VDC supply voltage increases the safety and reliability of your installation.
 
Easy to use!
This sensor doesn't require any configuration. Once installed, it is ready to use. The default settings will do for most applications. If necessary, the settings can be adjusted via Modbus RTU. For example, a different output type can be selected to make it compatible with other devices: 0-10 VDC / 0-20 mA / 0-100 % PWM / Modbus RTU. Also the light intensity of the LEDs for status indication is adjustable. The Modbus register map provides a complete overview of all adjustable settings.
  
High quality
Each sensor is calibrated and tested in our factory. In the unlikely event of CO/NO2 sensor element failure, this module can be replaced. We use sensor elements and components of high quality. This ensures the long-term stability and accuracy of this HVAC transmitter. The enclosure offers an IP30 protection against ingress of dust and moisture. It can be mounted on a wall indoors. To ensure optimal performance, it should be protected from direct sunlight.